| GCS AC low voltage power distribution cabinet |
| Application | |
| GCS series applied to power plants, petroleum, chemical,
metallurgy, textile, building and industry |
|
Main technical parameters | |
| Serial number | Name | Unit | Project | Parameter | | 1 | Main circuit rated voltage | V | | Exchange380、660 | | 2 | Rated voltage auxiliary circuit | V | | Exchange220、380DC110、220 | | 3 | Rated frequency | Hz | | 50(60) | | 4 | Rated insulation voltage | V | | 660(1000) | | 5 | Rated Current | A | Horizontal Bus | <4000 | | Vertical Bus(MCC) | 1000 | | 6 | Rated short time withstand current bus | kA/1s | | 50、80 | | 7 | Rated peak withstand current bus | kA/0.1s | | 105、176 | | 8 | Frequency test voltage | V/1min | Main circuit | 2500 | | Auxiliary circuit | 1760 | | 9 | Bus bar | | Three-phase four-wire system | A、B、C、PEN | | Three-phase five-wire system | A、B、C、PE、N | | 10 | Protection class | | | IP30、IP40 |
|
| Structural characteristics | |
| 1, the device uses 8MF steel main frame, frame by assembling and
welding two part structure. Are installed on the main frame modulus
hole E = 20m rTI2, device strictly separate the function room,
which features a single compartment is divided into no room, bus
room, cable rooms, each unit features independent. 3 drawer
changing only the height change, its width, depth unchanged. The